Chiller 3
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
Unit visually inspected and found in fair to good overall condition. Chilled water supply temperature measured at 1°C and return temperature at 7°C. Chilled water temperature difference of 6°C, indicating good heat absorption across the system. Supply water pressure recorded at 30 PSI (2.07 bar). Three-phase electrical current measured at 91.7 A, 90.6 A and 88.2 A, with an average of 90.17 A and good phase balance. Condenser coils show minor dust accumulation and signs of weather exposure. Chilled water piping insulation shows visible deterioration, particularly around fittings and connections. Pressure gauges show signs of aging and reduced readability. Chilled water supply temperature of 1°C is unusually low and may increase freezing risk if the system operates with untreated water.
Technical Details
- System
- Mechanical
- Category
- Chiller
- Manufacturer
- TRane
- Model
- RTAC 400 J
- Serial Number
- N/A
- Location
- —