ATH-000469Al-Salam

FAHU #02A

Status

Operational

Priority

P3 - Routine

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Winter condition during testing > 22 Celsius @54% RH - Actual Airflow Measured > 2.2 m³/s > 4729 CFM - ESP Measured > 580 Pa ; Possible airflow restriction and reduction of required airflow. REQUIRED AIRFLOW AS PER DRAWINGS: 8850 CFM - Psychrometric readings pre-coil @49.7% RH & 23.5 Celsius: Dry-bulb(Input) 23.5 °C RH(Input) 49.7 % Humidity ratio 8.96 g/kg Enthalpy 46.5 kJ/kg Wet-bulb 16.6 °C Dew point 12.4 °C Specific volume 0.852 m³/kg Density 1.184 kg/m³ Vapor pressure 1440 Pa - Psychrometric readings post-coil @84.7% RH & 13.6 Celsius: Dry-bulb(Input) 13.6 °C RH(Input) 84.7 % Humidity ratio 8.20 g/kg Enthalpy 34.4 kJ/kg Wet-bulb 12.1 °C Dew point 11.1 °C Specific volume 0.823 m³/kg Density 1.225 kg/m³ Vapor pressure 1319 Pa Calculations: Total cooling load > 9.1 TR Sensible cooling load > 7.6 TR Latent cooling load > 1.5 TR FINDINGS: Actual measured airflow is 4,729 CFM compared to the required 8,850 CFM, representing a 46.6% airflow shortfall. Measured ESP is 580 Pa. Possible airflow restriction within the return or supply duct system. Actual cooling capacity measured at 9.1 TR under winter operating conditions. Unit is operating at approximately 520 CFM/TR under the measured conditions. Overall, unit is in decent physical condition, however, airflow performance is significantly below the design requirement.

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
TRane
Model
CLCP EURO 012
Serial Number
—
Location
—

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update