FAHU #2B
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Winter conditions during testing > 53% RH & 22 Celsius - Actual Airflow Measured > 1.7 m³/s > 3,626 CFM - ESP Measured > 210 Pa Psychrometric readings pre-coil @53% RH & 22 Celsius: Dry-bulb(Input) 22.0 °C RH(Input) 53.0 % Humidity ratio 8.72 g/kg Enthalpy 44.3 kJ/kg Wet-bulb 15.9 °C Dew point 12.0 °C Specific volume 0.848 m³/kg Density 1.190 kg/m³ Vapor pressure 1402 Pa Psychrometric readings post-coil @80.6% RH & 11.1 Celsius: Dry-bulb(Input) 11.1 °C RH(Input) 80.6 % Humidity ratio 6.61 g/kg Enthalpy 27.8 kJ/kg Wet-bulb 9.4 °C Dew point 7.9 °C Specific volume 0.814 m³/kg Density 1.237 kg/m³ Vapor pressure 1065 Pa Summary of calculations: Total cooling > 9.6 TR Sensible cooling load > 6.4 TR Latent cooling load > 3.2 TR FINDINGS: Unit is providing effective cooling under the measured winter operating conditions. Actual total cooling capacity measured at 9.6 TR, consisting of 6.4 TR sensible and 3.2 TR latent cooling. Pre-coil air temperature measured at 22°C, decreasing to 11.1°C post-coil, achieving a temperature reduction of 10.9°C. Humidity ratio reduced from 8.72 g/kg to 6.61 g/kg, indicating effective moisture removal and dehumidification across the cooling coil. Actual measured airflow is 3,626 CFM, with ESP measured at 210 Pa. Overall, the unit is operating in good cooling condition, with satisfactory temperature reduction and dehumidification performance under the current operating conditions.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- TRane
- Model
- CLCP EURO 012
- Serial Number
- 1M1213-07022
- Location
- —
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update