AtharAssetAsset Record
ATH-000471Al-Salam

AHU #03

Status

Operational

Priority

P3 - Routine

Condition grade 2

Good

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Blower motor measured amps > 7.5 A (No overcurrent detected against motor maximum allowable) - Measured ESP > 420 Pa - Actual Airflow Measured > 5,485 CFM (Satisfies design requirements) - Psychrometric readings pre-coil @33.5% RH & 22.7 Celsius: Dry-bulb 22.7 °C RH 33.5 % Humidity ratio 5.73 g/kg Enthalpy 37.4 kJ/kg Wet-bulb 13.4 °C Dew point 5.8 °C Specific volume 0.846 m³/kg Density 1.189 kg/m³ Vapor pressure 925 Pa Psychrometric readings post-coil @37.3% RH & 20.5 Celsius: Dry-bulb 20.5 °C RH 37.3 % Humidity ratio 5.57 g/kg Enthalpy 34.8 kJ/kg Wet-bulb 12.3 °C Dew point 5.4 °C Specific volume 0.839 m³/kg Density 1.198 kg/m³ Vapor pressure 900 Pa SUMMARY OF CALCULATIONS: Total cooling load > 2.3 TR ; at the time of testing during winter and thermostat normal condition at 24-25 Celsius

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
TRane
Model
CLCP EURO 012
Serial Number
1M1213-07023
Location
—

Documents

0

No documents attached.