FINDINGS & RECOMMENDED ACTION

Winter condition during testing > 42.9% RH % 19.1 Celsius - Unit was barely producing any cooling or heating due to thermostat being identical to ambient, little change in enthalpy. - Unit measured exactly 380 V for 380 V 3-Phase blower motor. - No overcurrent detected - No overheating detected. PSYCHROMETRIC READINGS POST-COUL SUPPLY DUCT @44.1% RH & 19.2 Celsius: D Dry-bulb 19.2 °C RH 44.1 % Humidity ratio 6.08 g/kg Enthalpy 34.7 kJ/kg Wet-bulb 12.3 °C Dew point 6.7 °C Specific volume 0.836 m³/kg Density 1.203 kg/m³ Vapor pressure 981 Pa

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
TRane
Model
CLCP EURO 016
Serial Number
1M1213-07024