AHU #3B
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
Winter condition during testing > 42.9% RH % 19.1 Celsius - Unit was barely producing any cooling or heating due to thermostat being identical to ambient, little change in enthalpy. - Unit measured exactly 380 V for 380 V 3-Phase blower motor. - No overcurrent detected - No overheating detected. PSYCHROMETRIC READINGS POST-COUL SUPPLY DUCT @44.1% RH & 19.2 Celsius: D Dry-bulb 19.2 °C RH 44.1 % Humidity ratio 6.08 g/kg Enthalpy 34.7 kJ/kg Wet-bulb 12.3 °C Dew point 6.7 °C Specific volume 0.836 m³/kg Density 1.203 kg/m³ Vapor pressure 981 Pa
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- TRane
- Model
- CLCP EURO 016
- Serial Number
- 1M1213-07024
- Location
- —