FAHU #04
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Measured ESP > 280 Pa - Actual Airflow Measured > 2.3 m³/s > 4,963 CFM - Measured blower motor amperage > 4.5 A against rated 7.4 A (No overcurrent detected) - Psychrometric readings pre-coil @46.2% RH & 24.2 Celsius: Dry-bulb(Input) 24.2 °C RH(Input) 46.2 % Humidity ratio 8.69 g/kg Enthalpy 46.5 kJ/kg Wet-bulb 16.6 °C Dew point 11.9 °C Specific volume 0.854 m³/kg Density 1.181 kg/m³ Vapor pressure 1396 Pa - Psychrometric readings post-coil @84.8% RH & 11.6 Celsius: Dry-bulb(Input) 11.6 °C RH(Input) 84.8 % Humidity ratio 7.19 g/kg Enthalpy 29.8 kJ/kg Wet-bulb 10.2 °C Dew point 9.1 °C Specific volume 0.816 m³/kg Density 1.234 kg/m³ Vapor pressure 1158 Pa Summary of calculations: Total cooling load > 13.1 TR Sensible cooling load > 10.1 TR Latent cooling load > 3 TR FINDINGS: - Unit is performing at 379 CFM/TR (Perfectly in comfort range) - Belt needs attention and replacement (Cut and worn out)
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- TRane
- Model
- CLCP EURO 010
- Serial Number
- 1M121307025
- Location
- —