AtharAssetAsset Record
ATH-000474Al-Salam

FAHU #05

Status

Operational

Priority

P3 - Routine

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Winter conditions during testing > 36.7% RH & 17.9 Celsius - Unit measured airflow > 3,643 CFM ; Suspected restricted airflow against design CFM of 5,800 CFM - Measured ESP > 620 Pa ; Abnormally high and indicator of restricted airflow (closed dampers, blocked filters etc...) - Psychrometric readings pre-coil @36.7% RH and 17.9 Celsius: Dry-bulb(Input) 17.9 °C RH(Input) 36.7 % Humidity ratio Set as input 4.66 g/kg Enthalpy Set as input 29.8 kJ/kg Wet-bulb Set as input 10.3 °C Dew point Set as input 2.9 °C Specific volume Set as input 0.831 m³/kg Density 1.209 kg/m³ Vapor pressure 753 Pa Psychrometric readings post-coil @32.3% RH & 21 Celsius: Dry-bulb(Input) 21.0 °C RH(Input) 32.3 % Humidity ratio Set as input 4.97 g/kg Enthalpy Set as input 33.8 kJ/kg Wet-bulb Set as input 11.9 °C Dew point Set as input 3.8 °C Specific volume Set as input 0.840 m³/kg Density 1.196 kg/m³ Vapor pressure 804 Pa FINDINGS: Heating coil is functioning and providing sensible heating during winter operation. Significant airflow restriction is affecting the unit's ventilation performance and air distribution. High duct resistance is placing additional operating demand on the blower system and reducing the delivered airflow. Overall, unit is rated in FAIR condition, with satisfactory heating operation but unsatisfactory airflow performance.

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
TRane
Model
CLCP EURO 012
Serial Number
1M1213-07026
Location
—

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update