FAHU #5B
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Winter conditions during testing > 50.4% RH & 23.9 Celsius - Actual Airflow Measured > 1.0 m³/s > 2,128 CFM - Measured ESP > 410 Pa ; Abnormally high (To verify against datasheet) - Blower motor measured Amps > 6.5 A (No overcurrent detected) - Differential pressure of chilled water > 2.1 Bar (Within normal operating range) - Blower motor pulley RPM measured > 3562 RPM - Expected fan pulley RPM > 2957 RPM - Actual fan pulley RPM > 2984 RPM Slippage > 0.9% (Acceptable) - Psychrometric readings pre-coil @50.4% RH & 23.9 Celsius: Dry-bulb(Input) 23.9 °C RH(Input) 50.4 % Humidity ratio 9.32 g/kg Enthalpy 47.8 kJ/kg Wet-bulb 17.0 °C Dew point 13.0 °C Specific volume 0.854 m³/kg Density 1.182 kg/m³ Vapor pressure 1495 Pa Psychrometric readings post-coil @79.1% RH & 10.8 Celsius: Dry-bulb(Input) 10.8 °C RH(Input) 79.1 % Humidity ratio 6.35 g/kg Enthalpy 26.9 kJ/kg Wet-bulb 9.0 °C Dew point 7.3 °C Specific volume 0.813 m³/kg Density 1.238 kg/m³ Vapor pressure 1025 Pa Summary of calculations: Total cooling load > 7.1 TR FINDINGS: Unit is providing effective cooling under the measured winter operating conditions, achieving approximately 7.1 TR total cooling capacity. Pre-coil air temperature measured at 23.9°C, decreasing to 10.8°C post-coil, achieving a temperature reduction of 13.1°C. Humidity ratio reduced from 9.32 g/kg to 6.35 g/kg, indicating effective cooling and dehumidification. Actual measured airflow is 2,128 CFM, with elevated ESP of 410 Pa, indicating increased resistance within the airflow path. Blower motor operating at 6.5 A with no overcurrent detected. Fan pulley RPM measured at 2,984 RPM against an expected 2,957 RPM, showing approximately 0.9% deviation and satisfactory speed transmission. CHW differential pressure measured at 2.1 bar, indicating a substantial pressure difference across the measured points. Overall, the unit is delivering good cooling performance, however, elevated ESP indicates airflow restriction within the duct system.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- TRane
- Model
- CLCP EURO 010
- Serial Number
- M1213-07027
- Location
- —
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update