AHU #06
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Winter conditions during testing > 43% RH & 19.7 Celsius - Supply duct pressure measured > 140 Pa - Voltage measured 380.1 V for 380 V rated 3-phase blower motor. - Airflow Measured > 7660 CFM against 7700 CFM required design requirement. - Psychrometric readings pre-coil @43% RH & 19.7 Celsius: D Dry-bulb 19.7 °C RH 43.0 % Humidity ratio 6.12 g/kg Enthalpy 35.3 kJ/kg Wet-bulb 12.6 °C Dew point 6.8 °C Specific volume 0.838 m³/kg Density 1.201 kg/m³ Vapor pressure 987 Pa - Psychrometric readings post-coil @34.2% RH & 23.8 Celsius: D Dry-bulb 23.8 °C RH 34.2 % Humidity ratio 6.25 g/kg Enthalpy 39.9 kJ/kg Wet-bulb 14.3 °C Dew point 7.1 °C Specific volume 0.850 m³/kg Density 1.184 kg/m³ Vapor pressure 1009 Pa Total heating load during testing conditions > 20 kW FINDINGS: - Unit is in excellent condition.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- TRane
- Model
- CLCP EURO 016
- Serial Number
- 1M1213-07028
- Location
- —
Documents
0No documents attached.