AtharAssetAsset Record
ATH-000477Al-Salam

FAHU #07

Status

Operational

Priority

P3 - Routine

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Winter conditions under testing > 49.7% RH & 23.5 Celsius: - Actual measured airflow > 2.6 m³/s > 5,603 CFM - ESP Measured > 100 Pa ; Loss of duct resistance which explains increased airflow possibility against required of 3,775 CFM - Measured blower motor amperage > 4.6 A, No overcurrent detected against 7.4 A rated. - Psychrometric readings pre-coil @49.7% RH & 23.5 Celsius: Dry-bulb(Input) 23.5°C RH(Input) 49.7% Humidity ratio 8.96g/kg Enthalpy 46.5kJ/kg Wet-bulb16.6°C Dew point 12.4°C Specific volume 0.852 m³/kg Density 1.184 kg/m³ Vapor pressure 1440 Pa - Psychrometric readings post-coil @84.7% RH & 13.6 Celsius: Dry-bulb(Input) 13.6 °C RH(Input) 84.7 % Humidity ratio 8.20 g/kg Enthalpy 34.4 kJ/kg Wet-bulb 12.1 °C Dew point 11.1 °C Specific volume 0.823 m³/kg Density 1.225 kg/m³ Vapor pressure 1319 Pa Summary of calculations: Total cooling load > 10.7 TR Sensible cooling load > 9 Latent cooling load > 1.7 TR FINDINGS: - High airflow measured vs specified (3,775 CFM) due to possible loss of resistance through-out the duct which explains the suspected low measured ESP of 100 Pa only. - To further confirm the loss of resistance through ducts, RPM of fan pulley was measured to be only 2598 RPM against 3470 rated motor pulley, despite the almost identical pulley-to-pulley diameters. (Belt was too loose)

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
TRane
Model
CLCP EURO 008
Serial Number
1MM1307059
Location
—

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update