FAHU # 08
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Winter condition during testing > 22 Celsius @54% RH - Actual Airflow Measured > 4.2 m³/s > 8,936 CFM - Measured ESP > 360 Pa - Blower motor amperage > 9.2 A (No value to represent rated on nameplate) - Blower motor 3-phase supply voltage measured > 389.6 V against 380 V (No overvoltage detected) - Fan pulley RPM measured at 2456 RPM is 16% higher than expected (1.22 pulley-to-pulley ratio * 1765 RPM actual motor RPM = 2117 RPM expected) - Psychrometric readings pre-coil @54% RH & 22 Celsius: Dry-bulb(Input) 22.0 °C RH(Input) 54.0 % Humidity ratio 8.89 g/kg Enthalpy 44.7 kJ/kg Wet-bulb 16.0 °C Dew point 12.3 °C Specific volume 0.848 m³/kg Density 1.190 kg/m³ Vapor pressure 1428 Pa - Psychrometric readings post-coil @80.4% RH & 9.9 Celsius: Dry-bulb(Input) 9.9 °C RH(Input) 80.4 % Humidity ratio 6.08 g/kg Enthalpy 25.3 kJ/kg Wet-bulb 8.2 °C Dew point 6.7 °C Specific volume 0.810 m³/kg Density 1.243 kg/m³ Vapor pressure 981 Pa Summary of calculations: Total cooling load > 27.8 TR Sensible cooling load > 17.7 TR Latent cooling load > 10.1 TR FINDINGS: Unit is providing effective cooling under winter operating conditions, achieving approximately 27.8 TR total cooling capacity. Pre-coil temperature measured at 22°C, decreasing to 9.9°C post-coil, achieving a temperature reduction of 12.1°C. Actual measured airflow is 8,936 CFM against 6,810 CFM required, representing approximately 31.2% excessive airflow. Measured ESP is 360 Pa. Blower motor current measured at 9.2 A, with rated amperage unavailable for comparison. Three-phase supply voltage measured at 389.6 V against 380 V rated, within acceptable operating tolerance. Fan pulley RPM measured at 2,456 RPM against 2,117 RPM expected, representing approximately 16% higher fan speed than calculated. Overall, unit is delivering good cooling performance, however, excessive airflow and fan speed indicate incorrect blower operating conditions.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- TRane
- Model
- CLCP EURO 014
- Serial Number
- 1M1213-07030
- Location
- —
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update