AtharAssetAsset Record
ATH-000479Al-Salam

FAHU # 10

Status

Operational

Priority

P3 - Routine

Condition grade 4

Poor

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Winter current conditions during testing > 52% RH & 22 Celsius - Actual Airflow Measured > 0.5 m³/s > 1,066 CFM - ESP Measured > 230 Pa - Return pressure measured > +30 Pa (Positive) - Measured blower motor amperage > 2.5 A against 3.20 A rated (No overcurrent detected) - Psychrometric readings pre-coil @52.9% RH % 21.9 Celsius: Dry-bulb(Input) 21.9 °C RH(Input) 52.9 % Humidity ratio 8.65 g/kg Enthalpy 44.0 kJ/kg Wet-bulb 15.8 °C Dew point 11.9 °C Specific volume 0.847 m³/kg Density 1.190 kg/m³ Vapor pressure 1391 Pa Psychrometric readings post-coil @52% RH & 23.3 Celsius: Dry-bulb(Input) 23.3 °C RH(Input) 52.0 % Humidity ratio 9.27 g/kg Enthalpy 47.0 kJ/kg Wet-bulb 16.8 °C Dew point 12.9 °C Specific volume 0.852 m³/kg Density 1.184 kg/m³ Vapor pressure 1488 Pa - Unit's apparent enthalpy of post-coil is higher than pre-coil > no effective cooling. FINDINGS: Pre-coil air temperature measured at 21.9°C, while post-coil temperature reached 23.3°C, indicating no effective cooling during operation. CHW supply pressure measured at 3.8 bar, while return pressure measured at 2.5 bar, giving a differential pressure of 1.3 bar. CHW return pressure gauge showed rapid and continuous fluctuations, indicating unstable pressure readings within the return line. Cooling demand was not established during testing, consistent with thermostat setpoint satisfaction and chilled water control valve remaining closed. Overall, the unit's blower is operational, however, no effective cooling was achieved under the measured conditions.

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
TRane
Model
CLCP EURO 004
Serial Number
N/A
Location
—

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update