ATH-000480Al-Salam

AHU # 11

Status

Operational

Priority

P3 - Routine

Condition grade 2

Good

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Winter conditions during testing > 38.4% RH & 21 Celsius - Measured ESP > 500 Pa ; Abnormal - Actual Airflow > 7,611 CFM - Measured Amps > 15.5 A - Measured Volts > 380.7 V - Psychrometric readings pre-coil @38.4% RH % 21 Celsius: D Dry-bulb 21.0 °C RH 38.4 % Humidity ratio 5.92 g/kg Enthalpy 36.2 kJ/kg Wet-bulb 12.9 °C Dew point 6.3 °C Specific volume 0.841 m³/kg Density 1.196 kg/m³ Vapor pressure 955 Pa Psychrometric readings post-coil @49.3% RH & 17.1 Celsius: Dry-bulb 17.1 °C RH 49.3 % Humidity ratio 5.96 g/kg Enthalpy 32.3 kJ/kg Wet-bulb 11.3 °C Dew point 6.4 °C Specific volume 0.830 m³/kg Density 1.212 kg/m³ Vapor pressure 961 Pa SUMMARY OF CALCULATIONS: Total cooling > 4.76 TR FINDINGS: Unit is performing as per design ESP and cooling load as per winter conditions and room thermostat setpoint. - Unit is in good condition.