ATH-000482Al-Salam

AHU # 13

Status

Operational

Priority

P3 - Routine

Condition grade 2

Good

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Actual Airflow > 6,190 CFM ; (7,000 CFM design requirement) - Amperage measured > 11 A against 14.4 A rated blower motor (No overcurrent detected) - Volt measured > 380.4 V for 380 V 3-Phase blower motor. - Psychrometric readings pre-coil @32.5% RH & 24.5 Celsius: D Dry-bulb 24.5 °C RH 32.5 % Humidity ratio 6.20 g/kg Enthalpy 40.4 kJ/kg Wet-bulb 14.5 °C Dew point 7.0 °C Specific volume 0.852 m³/kg Density 1.182 kg/m³ Vapor pressure 1000 Pa Psychrometric readings post-coil @71.7% RH & 10.1 Celsius: D Dry-bulb 10.1 °C RH 71.7 % Humidity ratio 5.49 g/kg Enthalpy 24.0 kJ/kg Wet-bulb 7.6 °C Dew point 5.2 °C Specific volume 0.809 m³/kg Density 1.242 kg/m³ Vapor pressure 886 Pa SUMMARY OF CALCULATIONS: Total cooling load > 16.28 TR Sensible cooling load > 14.58 TR Latent cooling load > 1.7 TR FINDINGS: - Unit is performing well given the winter conditions, airflow requirement, and thermostat setpoint.

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
TRane
Model
CLCP EURO 014
Serial Number
1M1213-07034
Location
—