AHU # 13
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Actual Airflow > 6,190 CFM ; (7,000 CFM design requirement) - Amperage measured > 11 A against 14.4 A rated blower motor (No overcurrent detected) - Volt measured > 380.4 V for 380 V 3-Phase blower motor. - Psychrometric readings pre-coil @32.5% RH & 24.5 Celsius: D Dry-bulb 24.5 °C RH 32.5 % Humidity ratio 6.20 g/kg Enthalpy 40.4 kJ/kg Wet-bulb 14.5 °C Dew point 7.0 °C Specific volume 0.852 m³/kg Density 1.182 kg/m³ Vapor pressure 1000 Pa Psychrometric readings post-coil @71.7% RH & 10.1 Celsius: D Dry-bulb 10.1 °C RH 71.7 % Humidity ratio 5.49 g/kg Enthalpy 24.0 kJ/kg Wet-bulb 7.6 °C Dew point 5.2 °C Specific volume 0.809 m³/kg Density 1.242 kg/m³ Vapor pressure 886 Pa SUMMARY OF CALCULATIONS: Total cooling load > 16.28 TR Sensible cooling load > 14.58 TR Latent cooling load > 1.7 TR FINDINGS: - Unit is performing well given the winter conditions, airflow requirement, and thermostat setpoint.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- TRane
- Model
- CLCP EURO 014
- Serial Number
- 1M1213-07034
- Location
- —