ATH-000483Al-Salam

AHU # 15

Status

Operational

Priority

P3 - Routine

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Measured ESP > 830 Pa - Measured Amps > 14 A (No overcurrent detected) - Measured voltage > 393.1 V (No overvoltage detected) - Measured air velocity supply duct > 11.21 m/s Psychrometric readings post-coil > 77.3% RH & 10.8 Celsius: Dry-bulb 10.8 °C RH 77.3 % Humidity ratio 6.21 g/kg Enthalpy 26.5 kJ/kg Wet-bulb 8.8 °C Dew point 7.0 °C Specific volume 0.812 m³/kg Density 1.239 kg/m³ Vapor pressure 1001 Pa FINDINGS: Abnormally high ESP indicates possible airflow restriction due to blocked filters, closed dampers or duct obstructions. High supply air velocity may cause excessive noise and turbulence within the ductwork. Low post-coil temperature indicates effective air cooling, although overall cooling capacity cannot be confirmed without pre-coil readings. Electrical readings appear within acceptable operating limits.