AHU # 16
Status
Operational
Priority
P3 - Routine
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Temperature reading pre-coil > 23.6 Celsius - Psychrometric and temperature readings post-coil > 44.6% RH & 20.7 Celsius: Dry-bulb 20.7 °C RH 44.6 % Humidity ratio 6.76 g/kg Enthalpy 38.0 kJ/kg Wet-bulb 13.6 °C Dew point 8.2 °C Specific volume 0.841 m³/kg Density 1.196 kg/m³ Vapor pressure 1089 Pa - Measured Voltage > 393.8 V for 380 V rated blower motor. - Measured Amps > 5.5 A for 7.87 A rated blower motor (No overcurrent detected). FINDINGS: Cooling temperature reduction of 2.9°C indicates limited sensible cooling under the recorded operating conditions. Relatively high supply air temperature may indicate low cooling demand, insufficient chilled water flow or cooling valve modulation. Electrical readings appear acceptable, with no blower motor overcurrent detected.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- TRane
- Model
- CLCP EURO 008
- Serial Number
- 1M1213-07036
- Location
- —
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.