ATH-000485Al-Salam

FAHU # 18

Status

Operational

Priority

P3 - Routine

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Measured ESP > 140 Pa - Measured Airflow > 8,505 CFM - Measured Amps > 21.6 A for 28.3 A rated blower motor (No overcurrent detected). - Measured voltage > 392 V for 380 V PSYCHROMETRIC READINGS PRE-COIL > 34.2% RH & 24.9 Celsius: Dry-bulb 24.9 °C RH 34.2 % Humidity ratio 6.68 g/kg Enthalpy 42.1 kJ/kg Wet-bulb 15.1 °C Dew point 8.1 °C Specific volume 0.853 m³/kg Density 1.180 kg/m³ Vapor pressure 1077 Pa PSYCHROMETRIC READINGS POST-COIL > 61.6% RH & 13.8 Celsius: D Dry-bulb 13.8 °C RH 61.6 % Humidity ratio 6.02 g/kg Enthalpy 29.1 kJ/kg Wet-bulb 10.0 °C Dew point 6.6 °C Specific volume 0.821 m³/kg Density 1.226 kg/m³ Vapor pressure 972 Pa SUMMARY OF CALCULATIONS: Total cooling load > 17.74 TR Sensible cooling load > 15.45 TR Latent cooling load > 2.29 TR FINDINGS: Unit demonstrates good cooling performance, with effective sensible and latent heat removal under the recorded operating conditions. Significant condensation confirms active moisture removal across the cooling coil. Excessive water accumulation on the floor indicates possible condensate drain blockage, damaged drain pan or improper drainage. Relatively low ESP may indicate reduced duct resistance, depending on the unit's design specifications. Blower motor electrical readings appear acceptable, with no overcurrent detected.

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
TRane
Model
CLCP EURO 030
Serial Number
1M1213-07037
Location
—

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update