FAHU # 19
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Psychrometric readings post-coil > 69.3% RH & 12.4 Celsius: Dry-bulb 12.4 °C RH 69.3 % Humidity ratio 6.19 g/kg Enthalpy 28.1 kJ/kg Wet-bulb 9.5 °C Dew point 6.9 °C Specific volume 0.817 m³/kg Density 1.232 kg/m³ Vapor pressure 998 Pa - Duct supply air velocity measured > 6.93 m/s - Measured ESP > 50 Pa ; Suspected loss of pressure and resistance, duct leakage. - Unit performed cooling of 10.5 Celsius delta ; Good - Measured voltage > 390.5 V for 380 V 3-Phase blower motor. - Measured Amps > 6 A for 7.8 A rated (No overcurrent detected)
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- TRane
- Model
- CLCP EURO 012
- Serial Number
- 1M1213-07038
- Location
- —