FAHU # Cathlab
Status
Operational
Priority
P3 - Routine
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Winter conditions during testing > 53.6% RH & 22.3 Celsius - Actual Airflow Measured > 0.56 m³/s > 1,190 CFM - Blower motor measured Amps > 4.9 A (No overcurrent detected) - Measured voltage > 382.9 Volts Psychrometric readings pre-coil @53.6% RH & 22.3 Celsius: Dry-bulb(Input) 22.3 °C RH(Input) 53.6 % Humidity ratio 8.99 g/kg Enthalpy 45.3 kJ/kg Wet-bulb 16.2 °C Dew point 12.4 °C Specific volume 0.849 m³/kg Density 1.188 kg/m³ Vapor pressure 1444 Pa Psychrometric readings post-coil @98.7% RH & 15.9 Celsius: Properties Copy table Dry-bulb(Input) 15.9 °C RH(Input) 98.7 % Humidity ratio 11.14 g/kg Enthalpy 44.2 kJ/kg Wet-bulb 15.8 °C Dew point 15.7 °C Specific volume 0.834 m³/kg Density 1.213 kg/m³ Vapor pressure 1783 Pa FINDINGS: Unit achieved a temperature reduction of 6.4°C, with abnormal post-coil relative humidity of 98.7%. Hot-water heating circuit found with disconnected pipe connections and deteriorated insulation. Heating circuit condition may be contributing to improper temperature control and reduced cooling effectiveness.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- TRane
- Model
- CLCP EURO 008
- Serial Number
- 1M1114-07156
- Location
- —
Documents
0No documents attached.