FAHU #OR delivary
Status
Operational
Priority
P3 - Routine
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Actual Airflow > 2,796 CFM for 1,886 CFM required. - Psychrometric readings pre-coil > 33.7% RH & 23.8 Celsius: Dry-bulb 23.8 °C RH 33.7 % Humidity ratio 6.16 g/kg Enthalpy 39.6 kJ/kg Wet-bulb 14.2 °C Dew point 6.9 °C Specific volume 0.850 m³/kg Density 1.184 kg/m³ Vapor pressure 994 Pa - Psychrometric readings post-coil > 29% RH & 26.7 Celsius: Dry-bulb 26.7 °C RH 29.0 % Humidity ratio 6.30 g/kg Enthalpy 42.9 kJ/kg Wet-bulb 15.4 °C Dew point 7.2 °C Specific volume 0.858 m³/kg Density 1.173 kg/m³ Vapor pressure 1016 Pa SUMMARY OF CALCULATIONS: AHU is performing heating load of about 5 kW.
Technical Details
- System
- Mechanical
- Category
- Air Handling Unit
- Manufacturer
- TRane
- Model
- CLCP EURO 006
- Serial Number
- N/A
- Location
- —
Documents
0No documents attached.