AtharAssetAsset Record
ATH-000489Al-Salam

FAHU #OR delivary

Status

Operational

Priority

P3 - Routine

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Actual Airflow > 2,796 CFM for 1,886 CFM required. - Psychrometric readings pre-coil > 33.7% RH & 23.8 Celsius: Dry-bulb 23.8 °C RH 33.7 % Humidity ratio 6.16 g/kg Enthalpy 39.6 kJ/kg Wet-bulb 14.2 °C Dew point 6.9 °C Specific volume 0.850 m³/kg Density 1.184 kg/m³ Vapor pressure 994 Pa - Psychrometric readings post-coil > 29% RH & 26.7 Celsius: Dry-bulb 26.7 °C RH 29.0 % Humidity ratio 6.30 g/kg Enthalpy 42.9 kJ/kg Wet-bulb 15.4 °C Dew point 7.2 °C Specific volume 0.858 m³/kg Density 1.173 kg/m³ Vapor pressure 1016 Pa SUMMARY OF CALCULATIONS: AHU is performing heating load of about 5 kW.

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
TRane
Model
CLCP EURO 006
Serial Number
N/A
Location
—

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.