ATH-000490Al-Salam

FAHU#01

Status

Operational

Priority

P3 - Routine

Condition grade 2

Good

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Winter conditions during testing > 70% RH & 17 Celsius - ESP Measured > 190 Pa - Voltage measured > 385.1 V; Normal - Actual Airflow Measured > 2.2 m³/s > 4,676 CFM Psychrometric readings pre-coil @70% RH & 17 Celsius: Dry-bulb(Input) 17.0 °C RH(Input) 70.0 % Humidity ratio Set as input 8.44 g/kg Enthalpy Set as input 38.5 kJ/kg Wet-bulb Set as input 13.7 °C Dew point Set as input 11.5 °C Specific volume Set as input 0.833 m³/kg Density 1.210 kg/m³ Vapor pressure 1357 Pa Psychrometric readings @83.8% RH & 11.4 Celsius: Dry-bulb(Input) 11.4 °C RH(Input) 83.8 % Humidity ratio Set as input 7.01 g/kg Enthalpy Set as input 29.2 kJ/kg Wet-bulb Set as input 10.0 °C Dew point Set as input 8.8 °C Specific volume Set as input 0.815 m³/kg Density 1.235 kg/m³ Vapor pressure 1130 Pa Summary of calculations: Total cooling load > 7.0 TR Sensible cooling > 4.3 TR Latent cooling load > 2.7 TR FINDINGS: - Unit is dehumidifying at 2.7 TR latent cooling load - No abnormality found during inspection.

Technical Details

System
Mechanical
Category
Air Handling Unit
Manufacturer
TRane
Model
CLCP EURO 012
Serial Number
N/A
Location
—

Documents

0

No documents attached.