ATH-000501Al-Salam
REF 05A
Status
Operational
Priority
P3 - Routine
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Actual Airflow measured > 3,113 CFM for 4900 CFM design. - Actual ESP measured 380 Pa for 500 Pa design S.P - No overcurrent or overvoltage detected (Seen in image) - Apparent loss of airflow and loss of static pressure.
Technical Details
- System
- Mechanical
- Category
- Fan
- Manufacturer
- Loren cook comoany
- Model
- 300ACRUX
- Serial Number
- 210SF16076-01/0028301
- Location
- —
Documents