AtharAssetAsset Record
ATH-000501Al-Salam

REF 05A

Status

Operational

Priority

P3 - Routine

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Actual Airflow measured > 3,113 CFM for 4900 CFM design. - Actual ESP measured 380 Pa for 500 Pa design S.P - No overcurrent or overvoltage detected (Seen in image) - Apparent loss of airflow and loss of static pressure.

Technical Details

System
Mechanical
Category
Fan
Manufacturer
Loren cook comoany
Model
300ACRUX
Serial Number
210SF16076-01/0028301
Location
—

Documents