ATH-000512Al-Salam
REF 14
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Actual Airflow Measured > 5,067 CFM for 3,523 CFM rated ; Suspected loss of duct resistance. - Measured voltage > 386.7 V for 380 V 3-Phase fan motor. FINDINGS: - Airflow exceeds design requirements by approximately 43.8%, indicating possible reduced duct resistance, excessive fan speed, or improper air balancing. - Excessive airflow may increase motor loading, energy consumption and noise levels. - Measured voltage is approximately 1.76% above rated voltage, which is within the commonly acceptable ±10% motor voltage tolerance.
Technical Details
- System
- Mechanical
- Category
- Fan
- Manufacturer
- Loren cook comoany
- Model
- 210ACRUH
- Serial Number
- 210SF16076-01/00320513
- Location
- —
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.