AtharAssetAsset Record
ATH-000551Al-Salam

Booster pump1

Status

Operational

Priority

P2 - Planned

Condition grade 2

Good

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Grundfos vertical multistage booster pump in generally good physical condition. - Measured voltage of 316 V at 50 Hz, consistent with the expected VFD voltage-to-frequency ratio (380 × 50/60 = 316.7 V). - Measured motor current approximately 5.5 A. - Schneider Electric VFD operating at 50.5 Hz, with no fault indication observed. - Minor surface corrosion detected around lower pump flange and pipe connections. - Check valve needs repairing, opposite flow occurs. - No major physical defects or water leakage observed.

Technical Details

System
Plumbing & Water
Category
Building Water Booster Pump
Manufacturer
Grundfos
Model
A97842056P31341
Serial Number
85UO7522
Location
—

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.