AtharAssetAsset Record
ATH-000552Al-Salam

Booster pump2

Status

Operational

Priority

P3 - Routine

Condition grade 2

Good

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Measured voltage of 316 V at 50 Hz, consistent with the expected VFD voltage-to-frequency ratio (380 × 50/60 = 316.7 V). - Measured motor current approximately 5.5 A. - Schneider Electric VFD operating at 50.5 Hz, with no fault indication observed. - Minor surface corrosion detected around lower pump flange and pipe connections. - No major physical defects or water leakage observed.

Technical Details

System
Plumbing & Water
Category
Building Water Booster Pump
Manufacturer
Grundfos
Model
A97842056P31342
Serial Number
85UO7523
Location
—

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.