ATH-000552Al-Salam
Booster pump2
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Measured voltage of 316 V at 50 Hz, consistent with the expected VFD voltage-to-frequency ratio (380 × 50/60 = 316.7 V). - Measured motor current approximately 5.5 A. - Schneider Electric VFD operating at 50.5 Hz, with no fault indication observed. - Minor surface corrosion detected around lower pump flange and pipe connections. - No major physical defects or water leakage observed.
Technical Details
- System
- Plumbing & Water
- Category
- Building Water Booster Pump
- Manufacturer
- Grundfos
- Model
- A97842056P31342
- Serial Number
- 85UO7523
- Location
- —
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.