AtharAssetAsset Record
ATH-000580ALS

Main Distribution Board 1

Location

Al-Salam Main Building

Status

Operational

Priority

P2 - Planned

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- MDB-01 measured voltage > 393.3 V average. - Measured current > 277.33 A average. - Calculated apparent power > 188.9 kVA. - Estimated transformer loading > 12.6% against 1,500 kVA rated capacity. - Current imbalance > 16.35%, indicating significant unequal phase loading. - Voltage imbalance > 0.17%, indicating well-balanced voltage supply. - Supply frequency > 60 Hz. - All three phase indicators illuminated and incoming circuit breaker indicated ON... - No active trip indication detected.

Technical Details

System
Electrical
Category
Power Distribution
Manufacturer
—
Model
SACEE1.2B
Serial Number
BE71154985
Location
Al-Salam Main Building

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update