ATH-000580ALS
Main Distribution Board 1
Location
Al-Salam Main Building
Status
Operational
Priority
P2 - Planned
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- MDB-01 measured voltage > 393.3 V average. - Measured current > 277.33 A average. - Calculated apparent power > 188.9 kVA. - Estimated transformer loading > 12.6% against 1,500 kVA rated capacity. - Current imbalance > 16.35%, indicating significant unequal phase loading. - Voltage imbalance > 0.17%, indicating well-balanced voltage supply. - Supply frequency > 60 Hz. - All three phase indicators illuminated and incoming circuit breaker indicated ON... - No active trip indication detected.
Technical Details
- System
- Electrical
- Category
- Power Distribution
- Manufacturer
- —
- Model
- SACEE1.2B
- Serial Number
- BE71154985
- Location
- Al-Salam Main Building
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.