UPS
Location
Al-Salam Main Building
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
Calculations: Average Input Voltage = 219.33 V Average Input Current = 37 A Average Output Current = 30.67 A Output Current Imbalance = 35.87% Actual Loading = (20 / 125) × 100 = 16% FINDINGS: operating at approximately 16% of its displayed rated capacity. No overload indicated. Significant output current imbalance between phases. Input current readings are balanced. Output voltage readings are balanced. Battery autonomy display indicates 5 minutes at full load. UPS is supplying the connected load.
Technical Details
- System
- Electrical
- Category
- UPS
- Manufacturer
- —
- Model
- B9000 FXS
- Serial Number
- N/A
- Location
- Al-Salam Main Building
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.