AtharAssetAsset Record
ATH-000599RELIP

GF - PACU - 3

Location

ROOF / GF

Status

Operational

Priority

P3 - Routine

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Actual measured airflow > 14,672 CFM - Actual measured ESP > 260 Pa - Blower motor measured Amps > 8.5 A against 15.4 A (NO OVERCURRENT DETECTED) - Measured Voltage > 390.1 V (normal range for 380 V 3-phase connection) - Psychrometric readings pre-coil @27.3% RH & 22.8 Celsius: Dry-bulb 22.8 °C RH 27.3 % Humidity ratio 4.69 g/kg Enthalpy 34.9 kJ/kg Wet-bulb 12.4 °C Dew point 3.0 °C Specific volume 0.845 m³/kg Density 1.189 kg/m³ Vapor pressure 758 Pa - Psychrometric readings post-coil @40.8% RH & 16.5 Celsius: Dry-bulb 16.5 °C RH 40.8 % Humidity ratio 4.74 g/kg Enthalpy 28.6 kJ/kg Wet-bulb 9.7 °C Dew point 3.1 °C Specific volume 0.827 m³/kg Density 1.215 kg/m³ Vapor pressure 766 Pa Summary of CALCULATIONS: - Total cooling > 14.8 TR FINDINGS: - Blower motor operating at 55.2% of its rated current with no overcurrent detected. - Supply voltage within the acceptable operating range. - Unit operating at approximately 991 CFM/TR, significantly above the typical comfort cooling range due to low cooling demand during winter conditions. - Cooling operation confirmed with a temperature drop of 6.3°C across the cooling coil. - Cooling is predominantly sensible with negligible dehumidification due to low entering air humidity.

Technical Details

System
Mechanical
Category
GF - PACU - 3
Manufacturer
Carrier
Model
5OTJ - 032-231S
Serial Number
18412804042
Location
ROOF / GF

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update