FF-PACU-3

Location

ROOF / FF

Status

Operational

Priority

P2 - Planned

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Measured ESP > 320 Pa - Measured airflow > 12,017 CFM - Supply of 5.13 g/kg humidity ratio and 31.2 kJ/kg of enthalpy. - Psychrometric readings @39.9% RH & 18.1 Celsius: Dry-bulb 18.1 °C RH 39.9 % Humidity ratio 5.13 g/kg Enthalpy 31.2 kJ/kg Wet-bulb 10.9 °C Dew point 4.3 °C Specific volume 0.832 m³/kg Density 1.208 kg/m³ Vapor pressure 829 Pa SUMMARY OF CALCULATIONS; Total cooling > 8.7 TR ; For supply and return low cooling demand condition. FINDINGS: - 1,381 CFM/TR current performance (Very high for such low cooling demand and high fixed airflow speed). - Blower motor cables left open and uninsulated/protected.. - No overcurrent detected. - No abnormal high ESP detected - Unit performed reduction of 4.7 Celsius and increase of 0.1 g/kg of humidity ratio. - Low supply air moisture content, contributing to dry indoor conditions during winter operation. - No significant humidification detected across the unit.

Technical Details

System
Mechanical
Category
Package Unit
Manufacturer
Carrier
Model
5OTJ - 032-231S
Serial Number
3812S04614
Location
ROOF / FF

Documents

0

No documents attached.