FF-PACU-3
Location
ROOF / FF
Status
Operational
Priority
P2 - Planned
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Measured ESP > 320 Pa - Measured airflow > 12,017 CFM - Supply of 5.13 g/kg humidity ratio and 31.2 kJ/kg of enthalpy. - Psychrometric readings @39.9% RH & 18.1 Celsius: Dry-bulb 18.1 °C RH 39.9 % Humidity ratio 5.13 g/kg Enthalpy 31.2 kJ/kg Wet-bulb 10.9 °C Dew point 4.3 °C Specific volume 0.832 m³/kg Density 1.208 kg/m³ Vapor pressure 829 Pa SUMMARY OF CALCULATIONS; Total cooling > 8.7 TR ; For supply and return low cooling demand condition. FINDINGS: - 1,381 CFM/TR current performance (Very high for such low cooling demand and high fixed airflow speed). - Blower motor cables left open and uninsulated/protected.. - No overcurrent detected. - No abnormal high ESP detected - Unit performed reduction of 4.7 Celsius and increase of 0.1 g/kg of humidity ratio. - Low supply air moisture content, contributing to dry indoor conditions during winter operation. - No significant humidification detected across the unit.
Technical Details
- System
- Mechanical
- Category
- Package Unit
- Manufacturer
- Carrier
- Model
- 5OTJ - 032-231S
- Serial Number
- 3812S04614
- Location
- ROOF / FF
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update