Fresh Air PACU
Location
ROOF
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Blower motor measured Amps > 4.9 A (No overcurrent detected) - Measured voltage > 391.7 V for 380 V 3-Phase blower motor. (Normal) - Measured airflow > 3,408 CFM - Psychrometric readings pre-coil @19.9% RH & 28.5 Celsius: Dry-bulb 28.5 °C RH 19.9 % Humidity ratio 4.79 g/kg Enthalpy 40.9 kJ/kg Wet-bulb 14.7 °C Dew point 3.3 °C Specific volume 0.861 m³/kg Density 1.167 kg/m³ Vapor pressure 775 Pa - Psychrometric readings post-coil @53.4% RH & 9.4 Celsius: Dry-bulb 9.4 °C RH 53.4 % Humidity ratio 3.89 g/kg Enthalpy 19.3 kJ/kg Wet-bulb 5.4 °C Dew point 0.4 °C Specific volume 0.805 m³/kg Density 1.246 kg/m³ Vapor pressure 630 Pa SUMMARY OF CALCULATIONS: - Total cooling > 11.8 TR against 13.7 TR RATED - Sensible cooling > 10.6 TR - Latent cooling > 1.2 TR FINDINGS: - Unit is performing close to its rated design capacity despite more forgiving entering conditions. - Unit is in good condition.
Technical Details
- System
- Mechanical
- Category
- Package Unit
- Manufacturer
- Zamil
- Model
- PY180
- Serial Number
- HSA101-00195382
- Location
- ROOF