2F-PACU-2
Location
ROOF / 2F
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Measured ESP > 310 Pa - Psychrometric readings at supply duct: Dry-bulb 16.4 °C RH 41.6 % Humidity ratio 4.80 g/kg Enthalpy 28.6 kJ/kg Wet-bulb 9.8 °C Dew point 3.3 °C Specific volume 0.827 m³/kg Density 1.216 kg/m³ Vapor pressure 776 Pa FINDINGS: - Supply air temperature of 16.4°C indicates active cooling operation. - Low supply air moisture content of 4.80 g/kg, equivalent to approximately 27% RH when the air reaches a room temperature of 23°C at Riyadh atmospheric pressure. - Dry supply air conditions may contribute to insufficient indoor humidity during winter operation.
Technical Details
- System
- Mechanical
- Category
- Package Unit
- Manufacturer
- Carrier
- Model
- 5OTJ - 032-231S
- Serial Number
- 3312S04045
- Location
- ROOF / 2F