AtharAssetAsset Record
ATH-000603RELIP

GF-PACU-2

Location

ROOF

Status

Operational

Priority

P3 - Routine

Condition grade 2

Good

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Measured ESP > 370 Pa FINDINGS: - Measured ESP > 370 Pa. - Unit achieved a temperature reduction of 8.9°C across the cooling coil, indicating effective cooling operation under current winter conditions. - Enthalpy reduction of 10 kJ/kg across the cooling coil. - Humidity ratio decreased by 0.37 g/kg, indicating limited dehumidification. - Cooling is predominantly sensible due to low entering air moisture content. - Low supply air humidity ratio of 4.81 g/kg may contribute to dry indoor conditions.

Technical Details

System
Mechanical
Category
Package Unit
Manufacturer
Carrier
Model
5OTJM-28B2
Serial Number
082350TJ28100690
Location
ROOF

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update