ATH-000604RELIP
FF-PACU-2
Location
ROOF / FF
Status
Operational
Priority
P3 - Routine
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Measured ESP > 220 Pa - Unit achieved a temperature reduction of 6°C across the cooling coil. - Enthalpy reduction of 6.2 kJ/kg across the cooling coil. - Negligible humidity ratio reduction of 0.02 g/kg, indicating almost entirely sensible cooling. - Low supply air humidity ratio of 4.44 g/kg may contribute to excessively dry indoor conditions during winter operation.
Technical Details
- System
- Mechanical
- Category
- Package Unit
- Manufacturer
- Carrier
- Model
- 5OTJM-28B2
- Serial Number
- 082350TJ2410D315
- Location
- ROOF / FF
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.