AtharAssetAsset Record
ATH-000605RELIP

GF-PACU-1

Location

ROOF / GF

Status

Operational

Priority

P3 - Routine

Condition grade 2

Good

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Measured ESP > 340 Pa - Unit achieved a temperature reduction of 5.2°C across the cooling coil. - Enthalpy reduction of 5.2 kJ/kg across the cooling coil. - Negligible humidity ratio increase of 0.05 g/kg, within measurement uncertainty. - Cooling operation is predominantly sensible under current winter conditions. - Low supply air humidity ratio of 4.63 g/kg may contribute to dry indoor conditions.

Technical Details

System
Mechanical
Category
Package Unit
Manufacturer
Carrier
Model
N/A
Serial Number
N/A
Location
ROOF / GF

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update