ATH-000605RELIP
GF-PACU-1
Location
ROOF / GF
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Measured ESP > 340 Pa - Unit achieved a temperature reduction of 5.2°C across the cooling coil. - Enthalpy reduction of 5.2 kJ/kg across the cooling coil. - Negligible humidity ratio increase of 0.05 g/kg, within measurement uncertainty. - Cooling operation is predominantly sensible under current winter conditions. - Low supply air humidity ratio of 4.63 g/kg may contribute to dry indoor conditions.
Technical Details
- System
- Mechanical
- Category
- Package Unit
- Manufacturer
- Carrier
- Model
- N/A
- Serial Number
- N/A
- Location
- ROOF / GF
Documents
0No documents attached.