FF-PACU-1
Location
ROOF / FF
Status
Partially Operational
Priority
P2 - Planned
Condition grade 4
Poor
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Measured ESP > 300 Pa - Measured Airflow > 5,553 CFM - Psychrometric conditions pre-coil: D Dry-bulb 20.1 °C RH 45.1 % Humidity ratio 6.58 g/kg Enthalpy 36.9 kJ/kg Wet-bulb 13.2 °C Dew point 7.8 °C Specific volume 0.840 m³/kg Density 1.199 kg/m³ Vapor pressure 1061 Pa - Psychrometric readings post-coil: D Dry-bulb 22.7 °C RH 60.2 % Humidity ratio 10.37 g/kg Enthalpy 49.2 kJ/kg Wet-bulb 17.5 °C Dew point 14.6 °C Specific volume 0.852 m³/kg Density 1.186 kg/m³ Vapor pressure 1661 Pa FINDINGS: - Unit operating in heating conditions with a temperature increase of 2.6°C. - Abnormal moisture addition detected during heating operation, with humidity ratio increasing by 3.79 g/kg. - Significant moisture addition of approximately 42.5 kg/hr, inconsistent with normal sensible heating operation. - Abnormal psychrometric performance indicates an uncontrolled moisture source within the air system, unless intentional humidification is active.
Technical Details
- System
- Mechanical
- Category
- Package Unit
- Manufacturer
- Carrier
- Model
- 5OTJM-28B2
- Serial Number
- 2312803992
- Location
- ROOF / FF