EMP-1 A.T.S
Location
Basment / Electrical Room
Status
Operational
Priority
P2 - Planned
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Measured phase-to-neutral voltage: 229.9 V / 229.3 V / 228.8 V. - Measured phase-to-phase voltage: 398.0 V / 396.5 V / 397.5 V. - Voltage readings are well balanced with approximately 0.21% imbalance. - Measured active power: 2.901 kW / 1.113 kW / 2.705 kW. - Total active power: 6.719 kW. - Uneven power distribution across the three phases, with significantly lower loading on L2. - Blue phase indicator lamp appears unlit despite voltage availability. - Panel and circuit breakers are in good physical condition.
Technical Details
- System
- Electrical
- Category
- Automatic Transfer Switch
- Manufacturer
- —
- Model
- N/A
- Serial Number
- N/A
- Location
- Basment / Electrical Room