FINDINGS & RECOMMENDED ACTION

- Measured current: L1 = 14.54 A, L2 = 13.37 A, L3 = 12.65 A. - Average current: 13.52 A. - Current imbalance of approximately 7.5%, possibly due to uneven load distribution. - Measured phase-to-phase voltage: 397.3 V, 395.4 V and 396.6 V. - Average voltage: 396.4 V with negligible voltage imbalance (0.26%). - Phase-to-neutral voltage readings are unclear and require verification. - Panel enclosure is in good physical condition.