ATH-000610RELIP
EMP-2 A.T.S
Location
Basment / Electrical Room
Status
Operational
Priority
P4 - Monitor
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Measured current: L1 = 14.54 A, L2 = 13.37 A, L3 = 12.65 A. - Average current: 13.52 A. - Current imbalance of approximately 7.5%, possibly due to uneven load distribution. - Measured phase-to-phase voltage: 397.3 V, 395.4 V and 396.6 V. - Average voltage: 396.4 V with negligible voltage imbalance (0.26%). - Phase-to-neutral voltage readings are unclear and require verification. - Panel enclosure is in good physical condition.
Technical Details
- System
- Electrical
- Category
- Automatic Transfer Switch
- Manufacturer
- —
- Model
- N/A
- Serial Number
- N/A
- Location
- Basment / Electrical Room
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.