ATH-000611RELIP
MP - 1
Location
Basment / Electrical Room
Status
Operational
Priority
P3 - Routine
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Measured phase-to-phase voltage: 398.3 V, 397.2 V and 397.8 V. - Measured phase-to-neutral voltage: 230.4 V, 229.6 V and 229.2 V. - Voltage distribution is balanced with negligible imbalance of 0.14%. - Current imbalance of 10.9% based on displayed readings as shown in image attached in report. - Yellow phase indication lamp is not illuminated despite voltage being present. - Panel and circuit breakers are in good external physical condition. - Circuits are clearly labelled.
Technical Details
- System
- Electrical
- Category
- Electrical Panel
- Manufacturer
- —
- Model
- N/A
- Serial Number
- N/A
- Location
- Basment / Electrical Room