MDP -UPS
Location
Basment / Electrical Room
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Measured phase-to-phase voltages: 401.3 V, 401.4 V and 400.7 V. - Measured phase-to-neutral voltages: 231.4 V, 231.9 V and 231.5 V. - Voltage approximately 5.6% above the rated voltage, with negligible voltage imbalance. - Measured phase currents: 14.53 A, 6.463 A and 10.19 A. - Current imbalance of approximately 39.8% observed between phases. - No overloading detected against the rated main breaker capacity of 125 A. - Line 3 indicator lamp appears faulty despite voltage availability. - Panel enclosure is in good physical condition.