ATH-000652RELIP
MCC MAIN 800A
Location
2nd floor / Electrical Room
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Measured phase-to-neutral voltage: 231.0 V / 230.2 V / 229.3 V. - Measured phase-to-phase voltage: 399.7 V / 397.9 V / 399.1 V. - Measured current: 118.2 A / 117.0 A / 116.0 A. - Voltage and current readings are well balanced. - Current imbalance is approximately 0.97%. ; GOOD - Panel operating at approximately 14.6% of its rated current with no overloading detected.
Technical Details
- System
- Electrical
- Category
- Electrical Panel
- Manufacturer
- —
- Model
- N/A
- Serial Number
- N/A
- Location
- 2nd floor / Electrical Room
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update