AtharAssetAsset Record
ATH-000652RELIP

MCC MAIN 800A

Location

2nd floor / Electrical Room

Status

Operational

Priority

P3 - Routine

Condition grade 2

Good

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Measured phase-to-neutral voltage: 231.0 V / 230.2 V / 229.3 V. - Measured phase-to-phase voltage: 399.7 V / 397.9 V / 399.1 V. - Measured current: 118.2 A / 117.0 A / 116.0 A. - Voltage and current readings are well balanced. - Current imbalance is approximately 0.97%. ; GOOD - Panel operating at approximately 14.6% of its rated current with no overloading detected.

Technical Details

System
Electrical
Category
Electrical Panel
Manufacturer
—
Model
N/A
Serial Number
N/A
Location
2nd floor / Electrical Room

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.