ATH-000653RELIP

MCC MAIN 63A

Location

2nd floor / Electrical Room

Status

Operational

Priority

P3 - Routine

Condition grade 2

Good

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Main panel rated at 63 A, 380/220 V. - Measured phase-to-neutral voltage: 231.1 V / 230.2 V / 229.8 V. - Measured phase-to-phase voltage: 400.0 V / 398.0 V / 399.3 V. - Measured current: 8.593 A / 9.655 A / 8.046 A. - Voltage readings are well balanced. - Current imbalance of approximately 10.2% under low loading. - Panel operating at approximately 14% of its rated current with no overloading detected. - No active trip indications observed. - Panel and control switches are in good physical condition.

Technical Details

System
Electrical
Category
Electrical Panel
Manufacturer
—
Model
N/A
Serial Number
N/A
Location
2nd floor / Electrical Room