MCC MAIN 63A
Location
2nd floor / Electrical Room
Status
Operational
Priority
P3 - Routine
Condition grade 2
Good
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Main panel rated at 63 A, 380/220 V. - Measured phase-to-neutral voltage: 231.1 V / 230.2 V / 229.8 V. - Measured phase-to-phase voltage: 400.0 V / 398.0 V / 399.3 V. - Measured current: 8.593 A / 9.655 A / 8.046 A. - Voltage readings are well balanced. - Current imbalance of approximately 10.2% under low loading. - Panel operating at approximately 14% of its rated current with no overloading detected. - No active trip indications observed. - Panel and control switches are in good physical condition.
Technical Details
- System
- Electrical
- Category
- Electrical Panel
- Manufacturer
- —
- Model
- N/A
- Serial Number
- N/A
- Location
- 2nd floor / Electrical Room