ATH-000658RELIP
EXHAUST FAN 2
Location
ROOF
Status
Operational
Priority
P2 - Planned
Condition grade 3
Fair
1
2
3
4
5
FINDINGS & RECOMMENDED ACTION
- Airflow Measured > 3,128 CFM against 5000 CFM RATED - Measured ESP > 750 Pa FINDINGS: Severe airflow restriction in duct due to filter blockage.
Technical Details
- System
- Mechanical
- Category
- Exhaust Fan
- Manufacturer
- Saudi Fan
- Model
- DHW 500-4D-BC
- Serial Number
- 625964
- Location
- ROOF
Documents
0No documents attached.
Need to update this asset?
Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.
Sign in to update