AtharAssetAsset Record
ATH-000660RELIP

EXHAUST FAN - PHARMACY

Location

ROOF

Status

Operational

Priority

P2 - Planned

Condition grade 3

Fair

1

2

3

4

5

FINDINGS & RECOMMENDED ACTION

- Excessive airflow detected, exceeding design requirements by 73.8%. - Measured ESP is close to the rated operating pressure. - Excessive exhaust airflow may negatively affect room pressurization and increase cooling demand.

Technical Details

System
Mechanical
Category
Exhaust Fan
Manufacturer
Saudi Fan
Model
ERAE 225-4
Serial Number
625316
Location
ROOF

Documents

0

No documents attached.

Need to update this asset?

Sign in with your technician or administrator account. Your name and every changed field are added to the asset history.

Sign in to update